Original bilingual learning notes, researched from manufacturer resources. These are introductory checks, not complete model-specific service manuals. Reviewed 2 October 2026.
Before opening equipment, isolate power and verify it is off. Electrical testing and refrigerant handling are for qualified technicians. Stop if wiring is damaged, a protection repeatedly trips, or a refrigerant leak is suspected.
AC running, but not cooling
Confirm cooling mode and a setpoint below room temperature. Check for blocked supply and return openings.
Switch off before inspecting the filter. Clean or replace it according to the model instructions. Observe whether the outdoor coil is obstructed.
If cooling remains weak, a technician should investigate fans, icing and the refrigerant circuit. Weak cooling alone does not prove a refrigerant shortage.
Compare measured room temperature with the controller. Record recent warm deliveries and door openings. Inspect door seals and product clearance around the evaporator.
Observe fans, ice patterns and drainage. Review alarm history and defrost timing before changing settings.
Persistent faults require checks of sensors, refrigerant feed and operating conditions. Record evidence rather than replacing the expansion valve immediately.
With power isolated, inspect accessible coils and fan areas for dirt or obstruction. Clean using the equipment manufacturer’s method.
Check drainage and inspect for signs of oil around refrigeration connections. A technician should investigate suspected leaks.
After reassembly, observe normal cooling and defrost operation. Record temperatures and completed tasks; adapt the maintenance interval to the equipment and environment.
Identify the exact model before selecting a cleaning procedure. Remove stored ice before cleaning so chemicals cannot contaminate it.
Descaling and sanitizing have different purposes. Follow the model’s specified products, dilution, sequence and rinsing instructions. Never mix chemicals.
Inspect water quality and scale accumulation. Follow the model’s return-to-service procedure and record the cleaning date. Poor water conditions may require more frequent attention.
Use a pressure-temperature chart for the exact refrigerant. Do not confuse gauge pressure with absolute pressure.
For blends, use the dew-point saturation temperature for superheat and bubble-point temperature for subcooling.
Superheat is suction-pipe temperature minus saturation temperature. Subcooling is saturation temperature minus liquid-pipe temperature. Our calculators perform these differences; the manufacturer supplies the target.
Write down the date, equipment model, refrigerant, reported symptom, ambient conditions, measured temperatures, alarm codes, work done and results after restarting. Keep units beside every reading.
Official training videos
Videos in Portuguese and English, with language labels and bilingual topic notes. Portuguese subtitles for English videos are not verified. The written guides above can be used without loading a video. Clicking Load video connects to YouTube, which has its own privacy practices.
Daikin Brasil · Português
Air conditioner filter cleaning
Portuguese. Routine filter care from Daikin Brasil. Isolate power and follow the instructions for your model; internal deep cleaning requires a service technician.
English. Model-specific filter-cleaning demonstration. Check whether your filter is washable before using water. Portuguese subtitles are not verified.
English. Official Whirlpool guidance for French-door refrigerator coils. Disconnect power first and consult your model manual: condenser access and cleaning requirements vary.
Portuguese. Training for refrigeration technicians on choosing replacement components. Confirm refrigerant, electrical compatibility and the approved application before replacing parts.
Portuguese. Manufacturer demonstration for qualified refrigeration technicians, not a DIY procedure. Follow current model and refrigerant instructions; flammable refrigerants require specific training and equipment. Never vent refrigerant or apply heat to a charged system.
Inputs stay in your browser. Results are estimates, not equipment selection or manufacturer charging instructions.
HVAC / MOIST AIR
Psychrometric chart & calculator
Locate an air condition on the chart and calculate its moisture and energy properties.
Blue curves: relative humidity, 10–100%. Dashed lines: constant enthalpy, kJ/kg dry air. Orange A: inlet; green B: outlet. Connecting line indicates endpoints, not the exact coil process path. Purple lines: wet bulb (°C). Brown lines: specific volume (m³/kg dry air). Saturation-edge temperature labels also give dew point. The humidity scale starts at 0–30 g/kg and expands to include A and B. All property lines use the selected pressure.
Here w is kg water/kg dry air and h is kJ/kg dry air. Positive capacity means heat removed; negative means heat added. Positive water means moisture removed; negative means moisture added. Sensible/latent split uses outlet humidity ratio. SHR is shown only for cooling with non-negative sensible and latent components.
Steady flow at a common pressure, no dry-air leakage. Enter actual inlet volume, not standard-volume flow. Air-side estimate excludes condensate liquid enthalpy, fan heat outside the measurement points and equipment losses. It does not determine electrical input, COP, refrigerant charge or a complete building load.
Reading the results
Humidity ratio is water vapour mass per kilogram of dry air. Dew point indicates when cooling can begin to produce condensation. Wet-bulb temperature describes evaporative cooling potential. Enthalpy represents moist-air energy per kilogram of dry air.
Method and limits
PsychroLib equations based on ASHRAE Fundamentals. SI units; input range intentionally limited to common air-conditioning conditions. Estimates depend on sensor accuracy and pressure; this is not a complete cooling-load calculation.
The evaporator absorbs heat; the compressor raises vapour pressure; the condenser rejects heat; the expansion device reduces pressure. Identify the refrigerant and operating conditions before interpreting readings.
Air conditioning: first diagnostic checks
Record the symptom, mode, setpoint, return and supply temperatures, filter condition, airflow, drainage and outdoor conditions. Restricted airflow can mimic a refrigerant-circuit fault.
Cold rooms, fridges and freezers
Check door seals and closure, product arrangement, fans, evaporator ice, drainage and the defrost sequence. Record product and air temperatures; one isolated reading does not establish stability.
Maintenance and service records
Record equipment, serial number, refrigerant, date, before/after readings and work completed. Clean filters and heat exchangers to manufacturer instructions, check drainage, and schedule visits for the environment and duty.
Before servicing
Isolate power and verify absence of voltage before opening equipment. Electrical and refrigerant work requires qualified technicians, appropriate tools and manufacturer procedures. Do not mix refrigerants or charge by pressure alone.
Manufacturer resources
Use current manufacturer documentation for refrigerant tables, equipment limits and service procedures.