A practical reference for refrigeration and air-conditioning technicians. Check measurements, understand the system and document your work.

COOLING BISSAU / REPAIR LIBRARY

Read it here. Use it in the field.

Original bilingual learning notes, researched from manufacturer resources. These are introductory checks, not complete model-specific service manuals. Reviewed 2 October 2026.

Before opening equipment, isolate power and verify it is off. Electrical testing and refrigerant handling are for qualified technicians. Stop if wiring is damaged, a protection repeatedly trips, or a refrigerant leak is suspected.

AC running, but not cooling

  1. Confirm cooling mode and a setpoint below room temperature. Check for blocked supply and return openings.
  2. Switch off before inspecting the filter. Clean or replace it according to the model instructions. Observe whether the outdoor coil is obstructed.
  3. If cooling remains weak, a technician should investigate fans, icing and the refrigerant circuit. Weak cooling alone does not prove a refrigerant shortage.

Supporting reference: Carrier ↗

Cold room warm or repeatedly icing

  1. Compare measured room temperature with the controller. Record recent warm deliveries and door openings. Inspect door seals and product clearance around the evaporator.
  2. Observe fans, ice patterns and drainage. Review alarm history and defrost timing before changing settings.
  3. Persistent faults require checks of sensors, refrigerant feed and operating conditions. Record evidence rather than replacing the expansion valve immediately.

Supporting reference: Danfoss ↗

Fridge and freezer maintenance

  1. With power isolated, inspect accessible coils and fan areas for dirt or obstruction. Clean using the equipment manufacturer’s method.
  2. Check drainage and inspect for signs of oil around refrigeration connections. A technician should investigate suspected leaks.
  3. After reassembly, observe normal cooling and defrost operation. Record temperatures and completed tasks; adapt the maintenance interval to the equipment and environment.

Supporting reference: Heatcraft ↗

Ice-machine hygiene

  1. Identify the exact model before selecting a cleaning procedure. Remove stored ice before cleaning so chemicals cannot contaminate it.
  2. Descaling and sanitizing have different purposes. Follow the model’s specified products, dilution, sequence and rinsing instructions. Never mix chemicals.
  3. Inspect water quality and scale accumulation. Follow the model’s return-to-service procedure and record the cleaning date. Poor water conditions may require more frequent attention.

Supporting reference: Hoshizaki ↗

Understanding superheat and subcooling

  1. Use a pressure-temperature chart for the exact refrigerant. Do not confuse gauge pressure with absolute pressure.
  2. For blends, use the dew-point saturation temperature for superheat and bubble-point temperature for subcooling.
  3. Superheat is suction-pipe temperature minus saturation temperature. Subcooling is saturation temperature minus liquid-pipe temperature. Our calculators perform these differences; the manufacturer supplies the target.

Supporting reference: Schneider Electric ↗

Recognising defrost methods

  1. Identify whether the unit uses air, electrical heaters or hot gas for defrost. These systems are not interchangeable.
  2. Record when icing starts, when defrost begins and whether the coil clears. Check the model documentation before interpreting the sequence.
  3. Do not apply a universal timer setting or bypass protective controls. Use the correct equipment procedure for further diagnosis.

Supporting reference: Heatcraft ↗

A useful service record

Write down the date, equipment model, refrigerant, reported symptom, ambient conditions, measured temperatures, alarm codes, work done and results after restarting. Keep units beside every reading.

Official training videos

Videos in Portuguese and English, with language labels and bilingual topic notes. Portuguese subtitles for English videos are not verified. The written guides above can be used without loading a video. Clicking Load video connects to YouTube, which has its own privacy practices.

Daikin Brasil · Português

Air conditioner filter cleaning

Portuguese. Routine filter care from Daikin Brasil. Isolate power and follow the instructions for your model; internal deep cleaning requires a service technician.

Read the guide ↑
If playback fails, open on YouTube ↗

DaikinEurope · English

Daikin Perfera: cleaning air filters

English. Model-specific filter-cleaning demonstration. Check whether your filter is washable before using water. Portuguese subtitles are not verified.

Read the guide ↑
If playback fails, open on YouTube ↗

Whirlpool / W Service · English

Refrigerator condenser-coil cleaning

English. Official Whirlpool guidance for French-door refrigerator coils. Disconnect power first and consult your model manual: condenser access and cleaning requirements vary.

Read the guide ↑
If playback fails, open on YouTube ↗

Embraco · Português

Selecting compressor replacement components

Portuguese. Training for refrigeration technicians on choosing replacement components. Confirm refrigerant, electrical compatibility and the approved application before replacing parts.

Read the guide ↑
If playback fails, open on YouTube ↗

Embraco · Português

Compressor replacement: professional training

Portuguese. Manufacturer demonstration for qualified refrigeration technicians, not a DIY procedure. Follow current model and refrigerant instructions; flammable refrigerants require specific training and equipment. Never vent refrigerant or apply heat to a charged system.

Read the guide ↑
If playback fails, open on YouTube ↗

Field calculators

Inputs stay in your browser. Results are estimates, not equipment selection or manufacturer charging instructions.

Cooling capacity

BTU/h = kW × 3412.141633; TR = kW ÷ 3.516852842

Thermal capacity, not electrical input. TR means refrigeration ton.

Enter your measurements, then calculate.

Temperature conversion

°F = °C × 9/5 + 32; K = °C + 273.15

Absolute temperature conversion. Temperature differences use a different conversion.

Enter your measurements, then calculate.

Superheat

SH = Tpipe − Tsaturation

Gauge pressure: atmospheric reference

Default is standard sea-level pressure. Adjust for local conditions when using gauge readings. Absolute readings do not use this offset.

Saturation range: −50 to 60 °C. CoolProp 7.2.0 HEOS tables, interpolated every 0.25 °C; blend composition is nominal. These are calculation limits, not equipment pressure limits. Property source · License

Use the correct refrigerant pressure-temperature chart and suction pressure at the measurement point. For blends, use dew point. Compare with manufacturer targets; this does not prescribe a refrigerant charge.

Enter your measurements, then calculate.

Subcooling

SC = Tsaturation − Tliquid

Gauge pressure: atmospheric reference

Default is standard sea-level pressure. Adjust for local conditions when using gauge readings. Absolute readings do not use this offset.

Saturation range: −50 to 60 °C. CoolProp 7.2.0 HEOS tables, interpolated every 0.25 °C; blend composition is nominal. These are calculation limits, not equipment pressure limits. Property source · License

Use condensing pressure and liquid temperature at corresponding points. For blends, use bubble point. Not applicable to transcritical gas cooling.

Enter your measurements, then calculate.

Air-side sensible cooling

Q = 1.2 × 1.005 × (m³/h ÷ 3600) × ΔT

Approximation: air density 1.2 kg/m³ and specific heat 1.005 kJ/(kg·K). Excludes latent cooling and humidity removal; not total AC capacity. Density changes with altitude and temperature.

Enter your measurements, then calculate.

Cold-room panel heat gain

Q = U × A × ΔT ÷ 1000

One surface or a group with the same U-value. Transmission only: add infiltration, product cooling/freezing, people, lights, fans, defrost and operating schedule for a full cold-room load.

Enter your measurements, then calculate.

Energy and operating cost

E = kW × hours/day × days; cost = E × tariff

Use measured average electrical input, not cooling capacity. Example tariff only: replace with your bill. Excludes fixed fees and taxes.

Enter your measurements, then calculate.

HVAC / MOIST AIR

Psychrometric chart & calculator

Locate an air condition on the chart and calculate its moisture and energy properties.

101.325 kPa is standard sea-level pressure. Use local station pressure, not a weather report corrected to sea level.

A → B process results

Properties at A and B

Blue curves: relative humidity, 10–100%. Dashed lines: constant enthalpy, kJ/kg dry air. Orange A: inlet; green B: outlet. Connecting line indicates endpoints, not the exact coil process path. Purple lines: wet bulb (°C). Brown lines: specific volume (m³/kg dry air). Saturation-edge temperature labels also give dew point. The humidity scale starts at 0–30 g/kg and expands to include A and B. All property lines use the selected pressure.

Capacity calculation and sign convention

ṁ = V̇A / (3600 × vA); Qtotal = ṁ(hA − hB); Qsensible = ṁ(1.006 + 1.86 × wB)(TA − TB); Qlatent = Qtotal − Qsensible; water = ṁ(wA − wB) × 3600.

Here w is kg water/kg dry air and h is kJ/kg dry air. Positive capacity means heat removed; negative means heat added. Positive water means moisture removed; negative means moisture added. Sensible/latent split uses outlet humidity ratio. SHR is shown only for cooling with non-negative sensible and latent components.

Steady flow at a common pressure, no dry-air leakage. Enter actual inlet volume, not standard-volume flow. Air-side estimate excludes condensate liquid enthalpy, fan heat outside the measurement points and equipment losses. It does not determine electrical input, COP, refrigerant charge or a complete building load.

Reading the results

Humidity ratio is water vapour mass per kilogram of dry air. Dew point indicates when cooling can begin to produce condensation. Wet-bulb temperature describes evaporative cooling potential. Enthalpy represents moist-air energy per kilogram of dry air.

Method and limits

PsychroLib equations based on ASHRAE Fundamentals. SI units; input range intentionally limited to common air-conditioning conditions. Estimates depend on sensor accuracy and pressure; this is not a complete cooling-load calculation.

PsychroLib · License

Technical reference

The refrigeration cycle

The evaporator absorbs heat; the compressor raises vapour pressure; the condenser rejects heat; the expansion device reduces pressure. Identify the refrigerant and operating conditions before interpreting readings.

Air conditioning: first diagnostic checks

Record the symptom, mode, setpoint, return and supply temperatures, filter condition, airflow, drainage and outdoor conditions. Restricted airflow can mimic a refrigerant-circuit fault.

Cold rooms, fridges and freezers

Check door seals and closure, product arrangement, fans, evaporator ice, drainage and the defrost sequence. Record product and air temperatures; one isolated reading does not establish stability.

Maintenance and service records

Record equipment, serial number, refrigerant, date, before/after readings and work completed. Clean filters and heat exchangers to manufacturer instructions, check drainage, and schedule visits for the environment and duty.

Before servicing

Isolate power and verify absence of voltage before opening equipment. Electrical and refrigerant work requires qualified technicians, appropriate tools and manufacturer procedures. Do not mix refrigerants or charge by pressure alone.

Manufacturer resources

Use current manufacturer documentation for refrigerant tables, equipment limits and service procedures.